[vc_row][vc_column width=”2/3″][vc_column_text]
Trojan T105 Battery
One of the most successful traction batteries available. Flooded/wet lead-acid battery. A lot of other companies copy this battery, beware of cheaper imitations.
Engineered to provide rugged durability and outstanding performance, this deep cycle battery is well suited for use in renewable energy systems where lowest life-cycle cost is the key consideration. This battery is part of Trojan’s Signature Line.
Material: Polypropylene[/vc_column_text][vc_column_text]
PRODUCT SPECIFICATION
VOLTAGE | TERMINAL Type** | Length | Width | HeightC | WEIGHT lbs. (kg) |
---|---|---|---|---|---|
6 VOLT | 5 | 10-3/8 (264) mm | 7-1/8 (181) mm | 10-7/8 (276) mm | 62 (28) |
BCI GROUP SIZE |
2-Hr Rate | 5-Hr Rate | 10-Hr Rate | 20-Hr Rate | 48-Hr Rate | 72-Hr Rate | 100-Hr Rate | 100-Hr Rate |
---|---|---|---|---|---|---|---|---|
GC2 | 146 AH | 185 AH | 207 AH | 225 AH | 240 AH | 245 AH | 250 AH | 1.50 kWh |
[/vc_column_text][/vc_column][vc_column width=”1/3″][contact-form-7 id=”2456″][/vc_column][/vc_row][vc_row][vc_column width=”1/2″][vc_column_text]
CHARGING INSTRUCTIONS
CHARGER VOLTAGE SETTINGS (at 77°f/25°c) | |
---|---|
Voltage per cell | |
Absorption charge | 2.35-2.45 |
Float charge | 2.20 |
Equalize charge | 2.58 |
Do not install or charge batteries in a sealed or non-ventilated compartment. Constant under or overcharging will damage the battery and shorten its life as with any battery.
OPERATIONAL DATA
Operating Temperature | Self Discharge | Specific Gravity |
---|---|---|
-4°F to 113°F (-20°C to +45°C). At temperatures below 32°F (0°C) maintain a state of charge greater than 60%. | Up to 4% per week | The specific gravity at 100% state-of-charge is 1.280 |
[/vc_column_text][/vc_column][vc_column width=”1/2″][vc_column_text]
TERMINAL CONFIGURATIONS
[/vc_column_text][vc_row_inner][vc_column_inner width=”1/2″][vc_column_text]
[/vc_column_text][/vc_column_inner][vc_column_inner width=”1/2″][vc_column_text]
L-Terminal
Terminal Height Inches (mm)
1-3/4 (43)
Torque Values in-lb (Nm)
100 – 120 (11 – 14)
Through-hole Diameter (mm)
3/8 (10)[/vc_column_text][/vc_column_inner][/vc_row_inner][/vc_column][/vc_row][vc_row][vc_column width=”1/1″][vc_column_text]
CHARGING TEMPERATURE COMPENSATION
To the Voltage Reading: Subtract 0.005 volt per cell (VPC) for every 1°C above 25°C or add 0.005 volt per cell for every 1°C below 25°C.
EXPECTED LIFE VS. TEMPERATURE
Chemical reactions internal to the battery are driven by voltage and temperature. The higher the battery temperature, the faster chemical reactions will occur. While higher temperatures can provide improved discharge performance the increased rate of chemical reactions will result in a corresponding loss of battery life. As a rule of thumb, for every 10°C increase in temperature the reaction rate doubles. Thus, a month of operation at 35°C is equivalent in battery life to two months at 25°C. Heat is an enemy of all lead acid batteries, FLA, AGM and gel alike and even small increases in temperature will have a major influence on battery life.
A. The amount of amp-hours (AH) a battery can deliver when discharged at a constant rate at 77°F (25°C) and maintain a voltage above 1.75 V/cell. Capacities are based on peak performance.
B. Dimensions are based on nominal size. Dimensions may vary depending on type of handle or terminal.
C. Dimensions taken from bottom of the battery to the highest point on the battery. Heights may vary depending on type of terminal.
** Additional terminals available.
Trojan’s battery testing procedures adhere to both BCI and IEC test standards.