[vc_row][vc_column width=”2/3″][vc_column_text]

Schneider Conext XW Rangeschneider conext xw

One solution for global power

Conext XW is an adaptable pure sine wave, single-phase and three-phase inverter/charger system with global grid-tie functionality and dual AC power inputs. Available solar charge controllers, monitoring, and automated generator control modules enable further adaptability. From single Conext XW unit to multiple clusters of units, up to 36 kW each, the Conext XW is a scalable system that allows for the integration of solar capacity as required.
Adaptable and scalable, the Schneider ElectricTM Conext XW system is the one solution for global grid-interactive and off-grid, residential and commercial, solar and backup power applications.[/vc_column_text][vc_column_text]Why choose the Schneider Conext XW Range?

schneider handshake True bankability

  • Warranty from a trusted partner with over 177 years of experience
  • World leader in industrial power drives, UPS and electrical distribution
  • Strong service infrastructure worldwide to support your global needs
schneider stock Higher return on investment

  • Harness the continuously declining production cost of solar power
  • Hybrid integration of generator reduces diesel fuel costs
schneider check Designed for reliability

  • Robust design through rigorous reliability testing (HALT)
  • Proven field performance: 7 years with high reliability, globally in multiple
    applications and environments
schneider string Flexible

  • Adapts to single and three-phase systems
  • Scales to 36kW for commercial or large electrification installations
  • Supports DC coupled and AC coupled solutions
schneider tools Easy to service

  • Remote monitoring and configuration
  • Replaceable boards and components
  • Global support
schneider gear Easy to install

  • Devices configure quickly into a stylish wall mounted system
  • Inverters connect both grid and generator power with dual AC input

[/vc_column_text][/vc_column][vc_column width=”1/3″][contact-form-7 id=”2456″][/vc_column][/vc_row][vc_row][vc_column width=”1/1″][vc_column_text]

Product Applications

[/vc_column_text][vc_row_inner][vc_column_inner width=”1/4″][vc_column_text]

Residential, backup power and grid-tie


[/vc_column_text][/vc_column_inner][vc_column_inner width=”1/4″][vc_column_text]
Off-grid solar

Off-grid solar


[/vc_column_text][/vc_column_inner][vc_column_inner width=”1/4″][vc_column_text]
Community electrification

Community electrification


[/vc_column_text][/vc_column_inner][vc_column_inner width=”1/4″][vc_column_text]
Small commercial, backup power and grid-tie

Small commercial, backup power and grid-tie


[/vc_column_text][/vc_column_inner][/vc_row_inner][/vc_column][/vc_row][vc_row][vc_column width=”1/1″][vc_column_text]

Device short name XW4024 230 50 XW4548 230 50 XW6048 230 50
Electrical specifications
Output power (continuous) at 40°C 4.0kVA 4.5kVA 6.0kVA
Output power (surge) at 40°C 8.0kVA (20 sec) 9.0kVA (15 sec) 12.0kVA (15 sec)
Output current 17.4A 19.6A 26.1A
Peak output current (rms) 35A 40A 53A
Input current at rated power 178A 96A 131A
Type of signal True sine wave True sine wave True sine wave
Automatic transfer relay 56A 56A 56A
Typical transfer time 8ms 8ms 8ms
DC input voltage (nominal) 25.2V 50.4V 50.4V
Input voltage limits 20 to 32V 40 to 64V 40 to 64V
Charging current 150A 85A 100A
Power factor corrected charging 0.98 0.98 0.98
Auxiliary relay output 0 to 12V, maximum 250mA DC 0 to 12V, maximum 250mA DC 0 to 12V, maximum 250mA DC
Power consumption (search mode) < 7W < 7W < 7W
AC input voltage (nominal) 230V +/- 3% 230V +/- 3% 230V +/- 3%
Input voltage limits (bypass/charge mode) 165 to 280V (230V nominal) 165 to 280V (230V nominal) 165 to 280V (230V nominal)
Frequency 50Hz +/- 0.1Hz 50Hz +/- 0.1Hz 50Hz +/- 0.1Hz
AC input frequency range (bypass/charge mode) 40 to 68Hz (50Hz nominal) 40 to 68Hz (50Hz nominal) 40 to 68Hz (50Hz nominal)
Total harmonic distortion (THD) < 5% at rated power < 5% at rated power < 5% at rated power
AC connections AC1 (Grid), AC2 (Generator) AC1 (Grid), AC2 (Generator) AC1 (Grid), AC2 (Generator)
AC input breaker 60A single-pole 60A single-pole 60A single-pole
Efficiency
Peak 94.0% 95.6% 95.4%
General specifications
IP degree of protection IP20 (sensitive electric components sealed inside enclosure)
Product weight 52.5kg (116.0lb) 53.5kg (118.0lb) 55.2kg (121.7lb)
Shipping weight 74.0kg (163.0lb) 75.0kg (165.0lb) 76.7kg (169.0lb)
Product dimensions (H x W x D) 58 x 41 x 23cm (23 x 16 x 9in) 58 x 41 x 23cm (23 x 16 x 9in) 58 x 41 x 23cm (23 x 16 x 9in)
Shipping dimensions (H x W x D) 71.1 x 57.2 x 39.4cm
(28.0 x 22.5 x 15.5in)
71.1 x 57.2 x 39.4cm
(28.0 x 22.5 x 15.5in)
71.1 x 57.2 x 39.4cm
(28.0 x 22.5 x 15.5in)
Device mounting Wall mount (backplate included) Wall mount (backplate included) Wall mount (backplate included)
Ambient air temperature for operation -25°C to 70°C (-13°F to 158°F) (power derated above 45°C (113°F)
System network and remote monitoring Available Available Available
Warranty 5 years 5 years 5 years
Part number 865-1045-61 865-1040-61 865-1035-61
Features and options
Display type Status LEDs indicate AC In status, faults/warnings, equalise mode, On/Off and equalise button battery level.
Three-character display indicates output power or charge current
Supported battery types Flooded (default), Gel, AGM, custom Flooded (default), Gel, AGM, custom Flooded (default), Gel, AGM, custom
Battery bank size 100 to 2000Ah (scaled to PV array size)
Battery temperature sensor Included Included
Non volitaile memory Yes Yes
Multiple unit configurations Single-phase: up to four parallel units. Three-phase: two units per phase
Regulatory approval
CE marked according to the following EU directives and standards:
EMC directive EN61000-6-1, EN61000-6-3, EN61000-3-2, EN61000-3-3
Low voltage directive EN50178
RCM marked and compliant AS 4777.2, AS 4777.3, AS/NZS 3100

Specifications are subject to change without notice.[/vc_column_text][/vc_column][/vc_row]