[vc_row][vc_column width=”2/3″][vc_column_text]

Power One Aurora Trio PVI 10.0 TL OutdoorPower One Aurora TRIO PVI 10.0 Outdoor Product
Power One Aurora Trio PVI 12.5 TL Outdoor

The three-phase 10.0 and 12.5 kW non-isolated inverter is an industry leader.
Designed for commercial usage, this three-phase inverter is highly unique in its ability to control the performance of the PV panels, especially during periods of variable weather conditions. This transformerless device has two independent MPPTs and efficiency ratings of up to 97.7%.
The wide input voltage range makes the inverter suitable to low power installations with reduced string size. It is available with an optional fully-integrated DC switch, fuse and remote controlled DC disconnect function. The unit is free of electrolytic capacitors, leading to a longer product lifetime.

Features

  •  ‘Electrolyte-free’ power converter to further increase the life expectancy and long term reliability
  • True three-phase bridge topology for DC/AC output converter
  • Each inverter is set on specific grid codes which can be selected in the field
  • Dual input sections with independent MPP tracking, allows optimal energy harvesting from two sub-arrays oriented in different directions
  • Wide input range
  • High speed and precise MPPT algorithm for real time power tracking and improved energy harvesting
  • Flat efficiency curves ensure high efficiency at all output levels ensuring consistent and stable performance across the entire input voltage and output power range
  • Outdoor enclosure for unrestricted use under any environmental conditions
  • Integrated DC disconnect switch in compliance with international Standards (-S Version)
  • RS-485 communication interface (for connection to laptop or datalogger)
  • Compatible with PVI-RADIOMODULE for wireless communication with Aurora PVI-DESKTOP

[/vc_column_text][/vc_column][vc_column width=”1/3″][contact-form-7 id=”2456″][/vc_column][/vc_row][vc_row][vc_column width=”1/1″][vc_column_text]

Power One Aurora Trio Block Diagram

power one aurora trio block diagram[/vc_column_text][/vc_column][/vc_row][vc_row][vc_column width=”1/2″][vc_column_text]

Power One Aurora TRIO PVI 10.0 TL Outdoor

power one aurora trio pvi 10.0 tl efficiency curve[/vc_column_text][/vc_column][vc_column width=”1/2″][vc_column_text]

Power One Aurora TRIO PVI 12.5 TL Outdoor

power one aurora trio pvi 12.5 tl efficiency curve[/vc_column_text][/vc_column][/vc_row][vc_row][vc_column width=”1/1″][vc_column_text]

Parameter PVI-10.0-TL-OUTD PVI-12.5-TL-OUTD
Input Side
Absolute Maximum DC Input Voltage (Vmax,abs) 900 V
Start-up DC Input Voltage (Vstart) 360 V (adj. 250…500 V)
Operating DC Input Voltage Range (Vdcmin…Vdcmax) 0.7 x V start…850 V
Rated DC Input Power (Pdcr) 10300 W 12800 W
Number of Independent MPPT 2
Maximum DC Input Power for each MPPT (PMPPTmax) 6800 W 8000 W
DC Input Voltage Range with Parallel Configuration of MPPT at Pacr 300…750 V 300…750 V
DC Power Limitation with Parallel Configuration of MPPT Linear Derating From MAX to Null [750V≤VMPPT≤850V]
DC Power Limitation for each MPPT with Independent
Configuration of MPPT at Pacr , max unbalance example
6800 W [380V≤VMPPT≤750V]
the other channel: Pdcr-6800W
[195V≤VMPPT ≤750V]
8000 W [445V≤VMPPT≤750V]
the other channel: Pdcr-8000W
[270V≤VMPPT ≤750V]
Maximum DC Input Current (Idcmax) / for each MPPT (IMPPTmax) 36.0 A / 18.0 A
Maximum Input Short Circuit Current for each MPPT 22.0 A
Number of DC Inputs Pairs for each MPPT 2 (-S Version) 3 (Standard or –FS Version)
DC Connection Type Tool Free PV Connector WM / MC4
Input Protection
Reverse Polarity protection Yes, from limited current source
Input Over Voltage Protection for each MPPT – Varistor 2
Photovoltaic Array Isolation Control According to local standard
DC Switch Rating for each MPPT (-S Version) 25 A / 1000 V
Fuse Rating (-FS Version) 10 A / 1000 V
Output Side
AC Grid Connection Type Three phase (Δ/Y)
Rated AC Power (Pacr) 10000 W 12500 W
Maximum AC Output Power (Pacmax) 11000 W(3) 13800 W
Rated AC Grid Voltage (Vac,r) 400 V
AC Voltage Range 320…480 V
Maximum AC Output Current (Iac,max) 16.6 A 20.0 A
Rated Output Frequency (fr) 50 Hz
Output Frequency Range (fmin…fmax) 47…53 Hz(2)
Nominal Power Factor (Cosphiac,r) > 0.995 (adj. ± 0.9)
Total Current Harmonic Distortion < 2%
AC Connection Type Screw terminal block
Output Protection
Anti-Islanding Protection According to local standard
Maximum AC Overcurrent Protection 19.0 A 22.0 A
Output Overvoltage Protection – Varistor 3 plus gas arrester
Operating Performance
Maximum Efficiency (ηmax) 97.8%
Weighted Efficiency (EURO/CEC) 97.1% / – 97.2% / –
Feed In Power Threshold 30.0 W
Stand-by Consumption < 10.0 W
Communication
Wired Local Monitoring PVI-USB-RS485_232 (opt.), PVI-DESKTOP (opt.)
Remote Monitoring PVI-AEC-EVO (opt.), AURORA-UNIVERSAL (opt.)
Wireless Local Monitoring PVI-DESKTOP (opt.) with PVI-RADIOMODULE (opt.)
User Interface 16 characters x 2 lines LCD display
Environmental
Ambient Temperature Range -25…+60°C (-13…+140°F)
with derating above 55°C (131°F)
-25…+60°C /-13…140°F
with derating above 50°C/122°F
Relative Humidity 0…100% condensing
Noise Emission < 50 db(A) @ 1 m
Maximum Operating Altitude without Derating 2000 m / 6560 ft
Physical
Environmental Protection Rating IP 65
Cooling Natural
Dimension (H x W x D) 716mm x 645mm x 222mm / 28.2” x 25.4” x 8.7”
Weight < 41.0 kg / 90.4 lb
Mounting System Wall bracket
Safety
Isolation Level Transformerless
Marking CE
Safety and EMC Standard EN 50178, AS/NZS3100, AS/NZS 60950, EN61000-6-2, EN61000-6-3, EN61000-3-11, EN61000-3-12
Grid Standard DK 5940, VDE 0126-1-1, G59, EN 50438, RD1663, AS 4777, BDEW
Available Product Variants
Standard PVI-10.0-TL-OUTD PVI-12.5-TL-OUTD
With DC Switch PVI-10.0-TL-OUTD-S PVI-12.5-TL-OUTD-S
With DC Switch and Fuse PVI-10.0-TL-OUTD-FS PVI-12.5-TL-OUTD-FS

1. The AC voltage range may vary depending on specific country grid standard
2. The Frequency range may vary depending on specific country grid standard
3. Limited to 10000 W for Benelux