Fronius IG Plus Inverters
The allrounder with maximum yield.
The Fronius IG Plus generation of inverters represents an evolution of the proven Fronius IG product family. Power categories from 2.6 to 12 kW promise suitability for every possible system size. With a maximum efficiency of 95.9%, the two phase Fronius IG Plus 55 V-2 5000W solar inverter is not only a high performing unit like all the inverters in the Fronius range, it is also smart-grid ready and features Fronius MIX™ technology to achieve maximum yield, even when operating in partial-load range.
[/vc_column_text][vc_column_text]
Technical data: Fronius IG Plus (25 V-1, 30 V-1, 35 V-1, 50 V-1, 55 V-1, 60 V-1)
Input Data | 25 V-1 | 30 V-1 | 35 V-1 | 50 V-1 | 55 V-1 | 60 V-1 |
---|---|---|---|---|---|---|
DC maximum power at cos φ = 1 | 2,740 W | 3,170 W | 3,710 W | 4,260 W | 5,260 W | 6,320 W |
Max. input current (Idc max) | 11.9 A | 13.8 A | 16.2 A | 18.6 A | 22.9 A | 27.5 A |
Max. array short circuit current | 17.9 A | 20.7 A | 24.3 A | 27.9 A | 34.4 A | 41.3 A |
Min. input voltage (Udc min) | 230 V | |||||
Feed-in start voltage (Udc start) | 260 V | |||||
Nominal input voltage (Udc,r) | 370 V | |||||
Max. input voltage (Udc max ) | 600 V | |||||
MPP voltage range (Umpp min – Umpp max) | 230 – 500 V | |||||
Number of DC inputs | 6 |
Output Data | 25 V-1 | 30 V-1 | 35 V-1 | 50 V-1 | 55 V-1 | 60 V-1 |
---|---|---|---|---|---|---|
AC-Nennleistung (Pac,r) | 2,600 W | 3,000 W | 3,500 W | 4,000 W | 5,000 W | 6,000 W |
Max. output power | 2,600 W | 3,000 W | 3,500 W | 4,000 W | 5,000 W | 6,000 W |
Max. output current (Iac max) | 11.3 A | 13.0 A | 15.2 A | 17.4 A | 21.7 A | 26.1 A |
Grid connection (Uac,r) | 1~NPE 230 V | |||||
Min. output voltage (Uac min) | 180 V | |||||
Max. output voltage (Uac max ) | 270 V | |||||
Frequency (fr) | 50 Hz / 60 Hz | |||||
Frequency range (fmin – fmax) | 46 – 65 Hz | |||||
Distortion factor | < 3 % | |||||
Power factor (cos φac,r) | 0.75 – 1 ind. / cap.1) |
[/vc_column_text][/vc_column][vc_column width=”1/3″][contact-form-7 id=”2456″][/vc_column][/vc_row][vc_row][vc_column width=”1/1″][vc_column_text]
General Data | 25 V-1 | 30 V-1 | 35 V-1 | 50 V-1 | 55 V-1 | 60 V-1 |
---|---|---|---|---|---|---|
Dimensions (height x width x depth) | 673 x 434 x 250 mm | 968 x 434 x 250 mm | ||||
Weight | 23.8 kg | 36.9 kg | ||||
Degree of protection | IP 54 2) | |||||
Protection class | 1 | |||||
Overvoltage category (DC / AC) | 2 / 3 | |||||
Night-time consumption | ca. 1 W | |||||
Inverter concept | HF transformer | |||||
Cooling | Regulated air cooling | |||||
Installation | Indoor and outdoor installation | |||||
Ambient temperature range | from -20°C to +55°C | |||||
Permitted humidity | 0 % to 95 % | |||||
DC connection technology | Screw terminal connection 1.5 mm2 – 16 mm2 | |||||
AC connection technology | Screw terminal connection 2.5 mm2 – 35 mm2 | |||||
Certificates and compliance with standards | DIN V VDE V 0126-1-1, ÖVE / ÖNORM E 8001-4-712, UTE C15-712-1, EN 50438, G83, G59, C 10 / 11, CER 06-190, CEI 0-21, AS 4777-1, AS 4777-2, AS 4777-3, VDE AR N 4105, Generating systems on the medium-voltage network (BDEW) |
Fronius IG Plus 25 V-1, Fronius IG Plus 55 V-1 and Fronius IG Plus 60 V-1 devices do not comply with the German medium-voltage directive. Fronius IG Plus 55 V-1 and Fronius IG Plus 60 V-1 are not certified in accordance with the German low-voltage directive.
1) country-specific 2) Please refer to the information in the operating instructions regarding correct installation of the inverter (e.g. IP 44 applies to Australia).[/vc_column_text][/vc_column][/vc_row][vc_row][vc_column width=”1/2″][vc_column_text]
Fronius IG Plus 50 V-1 Efficiency Curve
[/vc_column_text][/vc_column][vc_column width=”1/2″][vc_column_text]
Fronius IG Plus 50 V-1 Temperature Derating
[/vc_column_text][/vc_column][/vc_row][vc_row][vc_column width=”1/1″][vc_column_text]
Technical data: Fronius IG Plus (25 V-1, 30 V-1, 35 V-1, 50 V-1, 55 V-1, 60 V-1)
Efficiency | 25 V-1 | 30 V-1 | 35 V-1 | 50 V-1 | 55 V-1 | 60 V-1 |
---|---|---|---|---|---|---|
Max. efficiency | 95.7 % | 95.7 % | 95.7 % | 95.7 % | 95.7 % | 95.7 % |
European efficiency (ηEU) | 94.6 % | 94.8 % | 95.0 % | 95.0 % | 94.9 % | 95.0 % |
η at 5 % Pac,r1) | 87.5 / 87.3 / 86.8 % | 87.9 / 87.6 / 87.2 % | 88.2 / 88.1 / 87.4 % | 88.7 / 88.6 / 88.2 % | 89.7 / 90.3 / 89.6 % | 90.2 / 91.0 / 90.0 % |
η at 10 % Pac,r1) | 89.7 / 89.8 / 89.4 % | 90.4 / 90.8 / 90.2 % | 91.6 / 92.3 / 91.5 % | 92.1 / 92.7 / 92.1 % | 91.4 / 91.8 / 90.8 % | 92.3 / 92.2 / 91.6 % |
η at 20 % Pac,r1) | 93.0 / 93.6 / 92.8 % | 93.6 / 94.2 / 93.2 % | 94.1 / 94.6 / 93.4 % | 94.4 / 94.7 / 93.5 % | 93.9 / 94.1 / 92.9 % | 94.6 / 94.5 / 93.7 % |
η at 25 % Pac,r1) | 93.8 / 94.3 / 93.3 % | 94.3 / 94.6 / 93.5 % | 94.6 / 94.8 / 93.7 % | 94.8 / 94.9 / 94.0 % | 94.4 / 94.6 / 93.6 % | 94.8 / 94.9 / 94.2 % |
η at 30 % Pac,r1) | 94.4 / 94.8 / 93.6 % | 94.7 / 94.9 / 93.8 % | 94.9 / 95.0 / 94.1 % | 95.1 / 95.2 / 94.5 % | 94.6 / 94.6 / 94.0 % | 95.0 / 95.2 / 94.7 % |
η at 50 % Pac,r1) | 95.2 / 95.4 / 94.7 % | 95.2 / 95.5 / 94.9 % | 95.3 / 95.7 / 95.3 % | 95.2 / 95.7 / 95.3 % | 94.9 / 95.5 / 94.7 % | 95.3 / 95.5 / 94.9 % |
η at 75 % Pac,r1) | 95.2 / 95.7 / 95.3 % | 95.1 / 95.7 / 95.4 % | 94.9 / 95.6 / 95.4 % | 94.7 / 95.5 / 95.4 % | 95.0 / 95.6 / 94.9 % | 95.1 / 95.7 / 95.3 % |
η at 100 % Pac,r1) | 94.9 / 95.6 / 95.4 % | 94.7 / 95.5 / 95.4 % | 94.4 / 95.2 / 95.1 % | 94.0 / 95.0 / 95.0 % | 95.1 / 95.7 / 95.2 % | 94.7 / 95.5 / 95.3 % |
MPP adaptation efficiency | > 99.9 % |
Protective Equipment | 25 V-1 | 30 V-1 | 35 V-1 | 50 V-1 | 55 V-1 | 60 V-1 |
---|---|---|---|---|---|---|
DC insulation measurement | Warning/shutdown (depending on country setup) at RISO < 600 kOhm | |||||
Overload behavior | Operating point shift, power limitation | |||||
DC circuit breaker | Integrated |
Interfaces | 25 V-1 | 30 V-1 | 35 V-1 | 50 V-1 | 55 V-1 | 60 V-1 |
---|---|---|---|---|---|---|
Optional with Fronius Datamanager | WLAN, Ethernet, Modbus TCP, 6 digital inputs, 4 digital inputs/outputs, Datalogger, Webserver |
1) and at Umpp min / Udc,r / Umpp max.
Technical Data: Fronius IG Plus (55 V-2, 60 V-2, 70 V-2, 100 V-2)
Input Data | 55 V-2 | 60 V-2 | 70 V-2 | 100 V-2 |
---|---|---|---|---|
DC maximum power at cos φ = 1 | 5,260 W | 6,320 W | 6,880 W | 8,520 W |
Max. input current (Idc max) | 22.9 A | 27.5 A | 30.0 A | 37.1 A |
Max. array short circuit current | 34.4 A | 41.3 A | 45.0 A | 55.7 A |
Min. input voltage (Udc min) | 230 V | |||
Feed-in start voltage (Udc start) | 260 V | |||
Nominal input voltage (Udc,r) | 370 V | |||
Max. input voltage (Udc max) | 600 V | |||
MPP voltage range (Umpp min – Umpp max) | 230 – 500 V | |||
Number of DC inputs | 6 |
Output Data | 55 V-2 | 60 V-2 | 70 V-2 | 100 V-2 |
---|---|---|---|---|
AC nominal output (P ac,r) | 5,000 W | 6,000 W | 6,500 W | 8,000 W |
Max. output power | 5,000 VA | 6,000 VA | 6,500 VA | 8,000 VA |
Max. output current (Iac max) | 10.9 A | 13.0 A | 14.1 A (28.3 A)1) | 17.4 A (34.8 A)1) |
Grid connection (Uac,r) | 2~NPE 400 V / 230 V | 2~NPE 400 V / 230 V (1~NPE 230 V)1) | ||
Min. output voltage (Uac min) | 180 V | |||
Max. output voltage (Uac max) | 270 V | |||
Frequency (fr) | 50 Hz / 60 Hz | |||
Frequency range (fmin – fmax) | 46 – 65 Hz | |||
Distortion factor | < 3 % | |||
Power factor (cos φac,r ) | 0.75 – 1 ind. / cap.2) |
General Data | 55 V-2 | 60 V-2 | 70 V-2 | 100 V-2 |
---|---|---|---|---|
Dimensions (height x width x depth) | 968 x 434 x 250 mm | |||
Weight | 36.9 kg | |||
Degree of protection | IP 54 3) | |||
Protection class | 1 | |||
Overvoltage category (DC / AC) | 2 / 3 | |||
Night-time consumption | ca. 1 W | |||
Inverter concept | HF transformer | |||
Cooling | Regulated air cooling | |||
Installation | Indoor and outdoor installation | |||
Ambient temperature range | from -20°C to +55°C | |||
Permitted humidity | 0 % to 95 % | |||
DC connection technology | Screw terminal connection 1.5 mm2 – 16 mm2 | |||
AC connection technology | Screw terminal connection 2.5 mm2 – 35 mm2 | |||
Certificates and compliance with standards | DIN V VDE V 0126-1-1. ÖVE / ÖNORM E 8001-4-712. UTE C15-712-1. EN 50438. G83. G59. C 10 / 11. CER 06-190. CEI 0-21. AS 4777-1. AS 4777-2. AS 4777-3. VDE AR N 4105. Generating systems on the medium-voltage network (BDEW) |
Fronius IG Plus 55 V-2 and Fronius IG Plus 60 V-2 devices do not comply with the German medium-voltage directive.
1) Single-phase (opt.)
2) country-specific
3) Please refer to the information in the operating instructions regarding correct installation of the inverter (e.g. IG 44 applies to Australia).[/vc_column_text][/vc_column][/vc_row][vc_row][vc_column width=”1/2″][vc_column_text]
Fronius IG Plus 100 V-2 efficiency curve
[/vc_column_text][/vc_column][vc_column width=”1/2″][vc_column_text]
Fronius IG PLUS 100 V-2 temperature derating
[/vc_column_text][/vc_column][/vc_row][vc_row][vc_column width=”1/1″][vc_column_text]
Technical data: Fronius IG Plus (55 V-2, 60 V-2, 70 V-2, 100 V-2)
Efficiency | 55 V-2 | 60 V-2 | 70 V-2 | 100 V-2 |
---|---|---|---|---|
Max. efficiency | 95.7 % | 95.7 % | 95.7 % | 95.7 % |
European efficiency (ηEU) | 94.9 % | 95.0 % | 95.1 % | 95.2 % |
η at 5 % Pac.r1) | 89.7 / 90.3 / 89.6 % | 90.2 / 91.0 / 90.0 % | 90.4 / 91.1 / 90.3 % | 90.9 / 91.4 / 90.5 % |
η at 10 % Pac.r1) | 91.4 / 91.8 / 90.8 % | 92.3 / 92.2 / 91.6 % | 93.0 / 93.2 / 92.0 % | 93.6 / 93.7 / 92.5 % |
η at 20 % Pac.r1) | 93.9 / 94.1 / 92.9 % | 94.6 / 94.5 / 93.7 % | 94.7 / 94.7 / 94.0 % | 94.7 / 95.1 / 94.4 % |
η at 25 % Pac.r1) | 94.4 / 94.6 / 93.6 % | 94.8 / 94.9 / 94.2 % | 94.9 / 95.1 / 94.4 % | 94.9 / 95.3 / 94.8 % |
η at 30 % Pac.r1) | 94.6 / 94.6 / 94.0 % | 95.0 / 95. 2 / 94.7 % | 95.0 / 95.3 / 94.8 % | 94.9 / 95.4 / 95.0 % |
η at 50 % Pac.r1) | 94.9 / 95.5 / 94.7 % | 95.3 / 95.5 / 94.9 % | 95.3 / 95.5 / 94.9 % | 95.2 / 95.7 / 95.2 % |
η at 75 % Pac.r1) | 95.0 / 95.6 / 94.9 % | 95.1 / 95.7 / 95.3 % | 95.0 / 95.7 / 95.3 % | 94.7 / 95.5 / 95.3 % |
η at 100 % Pac.r1) | 95.1 / 95.7 / 95.2 % | 94.7 / 95.5 / 95.3 % | 94.5 / 95.4 / 95.2 % | 94.0 / 95.1 / 95.0 % |
MPP adaptation efficiency | > 99.9 % |
Protective Equipment | 55 V-2 | 60 V-2 | 70 V-2 | 100 V-2 |
---|---|---|---|---|
DC insulation measurement | Warning/shutdown (depending on country setup) at RISO < 600 kOhm | |||
Overload behaviour | Operating point shift, power limitation | |||
DC circuit breaker | Integrated |
Interfaces | 55 V-2 | 60 V-2 | 70 V-2 | 100 V-2 |
---|---|---|---|---|
Optional with Fronius Datamanager | WLAN, Ethernet, Modbus TCP, 6 digital inputs, 4 digital inputs/outputs, Datalogger, Webserver |
1) and at Umpp min / Udc,r / U mpp max.
Technical data: Fronius IG Plus (55 V-3 / 60 V-3 / 80 V-3 / 100 V-3 / 120 V-3 / 150 V-3)
Input Data | 55 V-3 | 60 V-3 | 80 V-3 | 100 V-3 | 120 V-3 | 150 V-3 |
---|---|---|---|---|---|---|
DC maximum power at cos φ = 1 | 5,250 W | 6,300 W | 7,360 W | 8,430 W | 10,590 W | 12,770 W |
Max. input current (Idc max) | 22.8 A | 27.5 A | 32.0 A | 36.7 A | 46.2 A | 55.6 A |
Max. array short circuit current | 34.2 A | 41.3 A | 48.0 A | 55.1 A | 69.3 A | 83.4 A |
Min. input voltage (Udc min) | 230 V | |||||
Feed-in start voltage (Udc start) | 260 V | |||||
Nominal input voltage (Udc,r ) | 370 V | |||||
Max. input voltage (Udc max) | 600 V | |||||
MPP voltage range (Umpp min – Umpp max) | 230 – 500 V | |||||
Number of DC inputs | 6 |
Outut Data | 55 V-3 | 60 V-3 | 80 V-3 | 100 V-3 | 120 V-3 | 150 V-3 |
---|---|---|---|---|---|---|
AC nominal output (P ac,r) | 5,000 W | 6,000 W | 7,000 W | 8,000 W | 10,000 W | 12,000 W |
Max. output power | 5,000 VA | 6,000 VA | 7,000 VA | 8,000 VA | 10,000 VA | 12,000 VA |
Max. output current (Iac max) | 7.3 A | 8.7 A | 10.2 A | 11.6 A | 14.5 A | 17.4 A |
Grid connection (Uac,r) | 3~NPE 400 V / 230 V | |||||
Min. output voltage (Uac min) | 180 V | |||||
Max. output voltage (Uac max) | 270 V | |||||
Frequency (fr) | 50 Hz / 60 Hz | |||||
Frequency range (fmin – fmax) | 46 – 65 Hz | |||||
Distortion factor | < 3 % | |||||
Power factor (cos φac,r ) | 0.75 – 1 ind. / cap. 1) |
General Data | 55 V-3 | 60 V-3 | 80 V-3 | 100 V-3 | 120 V-3 | 150 V-3 |
---|---|---|---|---|---|---|
Dimensions (height x width x depth) | 1,263 x 434 x 250 mm | |||||
Weight | 49.2 kg | |||||
Degree of protection | IP 542) | |||||
Protection class | 1 | |||||
Overvoltage category (DC / AC) | 2 / 3 | |||||
Night-time consumption | ca. 1 W | |||||
Inverter concept | HF transformer | |||||
Cooling | Regulated air cooling | |||||
Installation | Indoor and outdoor installation | |||||
Ambient temperature range | -20 – +55 °C | |||||
Permitted humidity | 0 % to 95 % | |||||
DC connection technology | Screw terminal connection, 1.5 – 16 mm2 | |||||
AC connection technology | Screw terminal connection, 2.5 – 35 mm2 | |||||
Certificates and compliance with standards | DIN V VDE V 0126-1-1, ÖVE / ÖNORM E 8001-4-712, UTE C15-712-1, EN 50438, G83, G59, C 10 / 11, CER 06-190, CEI 0-21, AS 4777-1, AS 4777-2, AS 4777-3, VDE AR N 4105, Generating systems on the medium-voltage network (BDEW) |
Fronius IG Plus 55 V-3, Fronius IG Plus 60 V-3 and Fronius IG Plus 80 V-3 devices do not comply with German medium-voltage directive.
1) country-specific
2) Please refer to the information in the operating instructions regarding correct installation of the inverte (e.g. IP 44 applies to Australia).[/vc_column_text][/vc_column][/vc_row][vc_row][vc_column width=”1/2″][vc_column_text]
Fronius IG Plus 150 V-3 efficiency curve
[/vc_column_text][/vc_column][vc_column width=”1/2″][vc_column_text]
Fronius IG PLUS 150 V-3 temperature derating
[/vc_column_text][/vc_column][/vc_row][vc_row][vc_column width=”1/1″][vc_column_text]
Technical data: Fronius IG Plus (55 V-3 / 60 V-3 / 80 V-3 / 100 V-3 / 120 V-3 / 150 V-3)
Efficiency | 55 V-3 | 60 V-3 | 80 V-3 | 100 V-3 | 120 V-3 | 150 V-3 |
---|---|---|---|---|---|---|
Max. efficiency | 95.9 % | 95.9 % | 95.9 % | 95.9 % | 95.9 % | 95.9 % |
European efficiency (ηEU) | 94.9 % | 95.0 % | 95.1 % | 95.3 % | 95.4 % | 95.4 % |
η at 5% Pac,r1) | 90.5 / 91.6 / 89.9 % | 90.7 / 91.6 / 90.1 % | 90.8 / 91.8 / 90.2 % | 91.7 / 91.9 / 90.3 % | 91.5 / 92.2 / 90.7 % | 91.8 / 92.5 / 91.1 % |
η at 10% Pac,r1) | 91.5 / 92.2 / 90.8 % | 91.8 / 92.5 / 91.1 % | 92.1 / 92.8 / 91.5 % | 93.1 / 93.1 / 92.0 % | 93.4 / 93.7 / 92.6 % | 94.0 / 94.3 / 93.2 % |
η at 20% P ac,r1) | 93.4 / 93.6 / 93.3 % | 94.1 / 94.3 / 93.2 % | 94.2 / 94.5 / 93.6 % | 94.3 / 94.9 / 94.2 % | 94.6 / 95.2 / 94.5 % | 94.7 / 95.1 / 94.6 % |
η at 25% Pac,r1) | 94.1 / 94.2 / 93.3 % | 94.4 / 94.7 / 93.8 % | 94.6 / 94.9 / 94.3 % | 94.6 / 95.2 / 94.5 % | 94.7 / 95.3 / 94.7 % | 95.1 / 95.3 / 94.7 % |
η at 30% P ac,r1) | 94.4 / 94.5 / 93.8 % | 94.5 / 95.0 / 94.4 % | 94.6 / 95.2 / 94.6 % | 94.7 / 95.2 / 94.5 % | 95.0 / 95.4 / 94.7 % | 95.1 / 95.3 / 94.9 % |
η at 50% P ac,r1) | 94.7 / 95.4 / 94.7 % | 95.1 / 95.4 / 94.6 % | 95.1 / 95.5 / 94.9 % | 95.3 / 95.8 / 95.0 % | 95.3 / 95.9 / 95.1 % | 95.3 / 95.9 / 95.3 % |
η at 75% Pac,r1) | 95.2 / 95.7 / 95.0 % | 95.3 / 95.7 / 95.0 % | 95.3 / 95.9 / 95.1 % | 95.3 / 95.9 / 95.3 % | 95.0 / 95.5 / 95.4 % | 94.7 / 95.6 / 95.4 % |
η at 100% Pac,r1) | 95.3 / 95.9 / 95.2 % | 95.3 / 95.9 / 95.3 % | 95.1 / 95.7 / 95.4 % | 94.9 / 95.7 / 95.4 % | 94.6 / 95.5 / 95.3 % | 94.0 / 95.2 / 95.1 % |
MPP adaptation efficiency | > 99.9 % |
Protective Equipment | 55 V-3 | 60 V-3 | 80 V-3 | 100 V-3 | 120 V-3 | 150 V-3 |
---|---|---|---|---|---|---|
DC insulation measurement | Warning/shutdown (depending on country setup) at RISO < 600 kOhm | |||||
Overload behaviour | Operating point shift, power limitation | |||||
DC circuit breaker | Integrated |
Interfaces | 55 V-3 | 60 V-3 | 80 V-3 | 100 V-3 | 120 V-3 | 150 V-3 |
---|---|---|---|---|---|---|
Optional with Fronius Datamanager | WLAN, Ethernet, Modbus TCP, 6 digital inputs, 4 digital inputs/outputs, Datalogger, Webserver |